Emergency UPS repair
When a UPS alarms, transfers to bypass or drops the load, the first job is to keep the load safe and the second is to get the right person and parts to site.

Equipment illustration
UPS in alarm or on bypass?
Call the 24/7 lineKey facts
- Who clears faults:
- Most faults and warnings must be released by service personnel, not users (XPC M90U manual)
- Common causes:
- Dust, humidity and heat wear electronic components (Eaton)
4 h Reply and quote: within 4 business hours
Same day Same day: Montreal, Quebec City, Toronto, Ottawa
24 to 48 h Elsewhere in Canada: 24 to 48 hours
24/7 Emergency line: 24/7
Emergency UPS Repair for Data Centres
First steps when a UPS alarms
Short answer
Note the alarm and the time, check whether the load is on inverter, battery or bypass, do not reset or transfer unless the manual allows it, and call the emergency line.
- Read the alarm on the display and note it exactly, with the time.
- Check whether the load is on inverter, on battery or on bypass.
- If it is on battery, check the battery time remaining and start an orderly shutdown plan if the outage will outlast it.
- Do not reset alarms or transfer the UPS unless the maker's manual and your procedure allow it; makers such as XPC note that most faults and warnings must be cleared by service personnel.
- Call the emergency line with the model, the alarm text, the load and what has changed.
Steps of an emergency repair
- What happensCall to the emergency lineWhat is recordedModel, alarm text, load state, time
- What happensTriage: load safety first, then the likely faultWhat is recordedAdvice given and parts identified
- What happensDispatch with the parts the fault needsWhat is recordedArrival time
- What happensDiagnosis on siteWhat is recordedCause found and readings
- What happensRepair to the maker's procedureWhat is recordedParts replaced and settings
- What happensTest and return to normalWhat is recordedTransfer back and final status
- What happensReport and preventionWhat is recordedCause, work done and recommendations
Repair report
Report layout, example
| Entry | Time | Alarm or event | Action | Result |
|---|---|---|---|---|
Report layout, example. Values are recorded on site.
- Call: The model, the alarm text, the load state and the time
- Diagnosis: The cause found and the readings taken
- Repair: Parts replaced, settings, and the transfer back to normal
- Prevention: What should be done to stop it happening again
Common causes of emergency calls
Most emergency calls trace back to batteries, heat or worn components. Schneider Electric's manual lists elevated temperature, poor utility power and frequent short discharges as causes of shortened battery life, and tells users to replace the battery when the UPS calls for it. Eaton's aging-UPS paper names dust, humidity and heat as the wear factors for electronics, and its maintenance guidance adds blocked air filters, which can shut a UPS down on overheating, and connections loosened by vibration.
Protecting the load during a repair
During a repair the load runs on the bypass path, on utility power without UPS conditioning. On some UPS the batteries are not available in maintenance bypass, as Schneider Electric notes for the Galaxy VS. The repair plan says how long the load will be on bypass, what the risk is, and whether the generator should be ready; see static and maintenance bypass.
After the call
We answer the emergency line around the clock, ask for the model, the alarm and the load state, and send the person and parts the fault needs, on site the same day in Montreal, Quebec City, Toronto or Ottawa and within 24 to 48 hours at other Canadian sites. On site the fault is diagnosed, the repair is made to the maker's procedure, and the UPS is returned to normal with the load transferred back once it is proven. The repair report records the cause, the parts replaced and what should be done to stop it happening again.
Preventing the next failure
Eaton's preventive maintenance guidance: air filters inspected every month, a scan for hot spots every three months, and capacitors planned for replacement at or near the end of their rated service life. Maintenance visits that compare each reading with a baseline find them early; see maintenance contracts. For battery replacement after a failure, compatible blocks are listed among these APC RBC battery cartridges; for repair by brand, see UPS repair by make and model.
Questions
Should I reset the alarm myself?
Only if the maker's manual and your site procedure allow it. Many faults must be cleared by service personnel, and a reset can hide the cause.
How fast can someone get to site?
The same day for sites in Montreal, Quebec City, Toronto or Ottawa, and in 24 to 48 hours for the rest of Canada, with the emergency line open day and night.
Can you repair any brand?
Three-phase UPS from the main makers, including Eaton, Schneider Electric (APC), Vertiv (Liebert), Mitsubishi Electric, Toshiba and Delta. Parts availability for older models is confirmed during triage.
What information speeds up the repair?
The model and serial number, the exact alarm text, whether the load is on inverter, battery or bypass, and what changed before the alarm.
Sources, checked 2026-10-04:
- Manual Xtreme Power Conversion, M90U user's manual, p. 62
- Manual Schneider Electric, Smart-UPS On-Line SRT2200XLA/SRT3000XLA operation manual, p. 4
- White paper Eaton, Your aging three-phase UPS: when to refresh, replace or run to fail (white paper WP161005EN, October 2021)
- Reference Eaton, Top five UPS components that require preventive maintenance
- Manual Schneider Electric, Galaxy VS UPS operation manual 990-5910G, p. 16