Fire protection
Data centre fire protection
The rooms that hold a data centre's UPS, its batteries and its switchgear are where electrical faults start and where water does the most damage.
Need the UPS in this room serviced? Get a quote
Key facts
- Clean agents:
- Electrically non-conductive, with no post-fire residue (Honeywell)
- Inert gas:
- Puts out fire by lowering the oxygen content below the level that supports combustion (Honeywell)
- Very early warning:
- Four alarm levels: Alert, Action, Fire 1 and Fire 2 (Xtralis)
- Agent and pressure check:
- At least once every six months (Honeywell, Firetrace)
- 3M and PFAS:
- 3M completed its exit of PFAS manufacturing at the end of 2025
UPS and battery rooms
UPS and battery rooms hold the equipment that keeps the data centre running, and the wrong extinguishing method can do as much harm as the fire. A UPS room combines power electronics, battery strings and cabling under load; a sprinkler discharge there means wet electrical equipment and a long outage even when the fire was small. Gas-based clean-agent systems were developed for these spaces. Honeywell's manual describes them as designed for hazards where an electrically non-conductive agent is required, where agent clean-up creates a problem and where the room is normally occupied.
See the UPS and battery room fire protection guide for what a fire, or a discharge, means for the UPS and the batteries.
Clean agents
Clean agents come in two families: halocarbon agents such as HFC-227ea and FK-5-1-12, and inert gases such as IG-541 and IG-55. The halocarbons are discharged in seconds; Honeywell's FK-5-1-12 systems are designed to discharge in 6 to 10 seconds. Inert gases take longer and work by lowering the oxygen level; Honeywell's IG-541 systems discharge in 60 to 120 seconds. See the clean-agent systems guide for how each works, where each fits, and what 3M's exit from PFAS manufacturing means for FK-5-1-12.
Early warning detection
Early warning detection acts before any agent is released. Aspirating detection such as VESDA draws air from the room through sampling pipes and can raise an alert while smoke is still invisible. Xtralis' specification gives four alarm levels, with the second one able to trip an equipment shutdown relay and the fourth able to release the suppression system. See VESDA and aspirating early warning detection.
Keeping a system ready
A clean-agent system is kept ready by regular checks of the agent quantity and pressure, the controls and the room itself. Both manufacturer manuals cited here call for the agent quantity and pressure to be checked at least every six months. See clean-agent inspection for the full schedule and what each visit records.
In this section
Clean-agent fire suppression systems
How each agent works, where each fits, and the FK-5-1-12 supply question.
VESDA and aspirating early warning detection
Air sampling, four alarm levels, and how they link to the UPS.
What an NFPA 2001 clean-agent inspection covers
Monthly, six-monthly, yearly and five-year checks.
Fire protection for UPS and battery rooms
Battery gases, lithium-ion rules, interlocks, and the UPS after a discharge.
Questions
Can a sprinkler system protect a UPS room?
Sprinklers are often required by code, and for lithium-ion battery rooms Vertiv notes that the 2018 edition of NFPA 1 requires them. A clean-agent system is usually added to protect the electrical equipment from fire without water damage.
Is FK-5-1-12 still available after 3M's exit?
3M completed its exit of PFAS manufacturing at the end of 2025. The US EPA's list names FK-5-1-12 under several trade names besides Novec 1230, so for an existing system, ask the system's maker which agent source it lists for refills.
How often is a clean-agent system inspected?
The agent quantity and pressure are checked at least every six months, and the whole system is inspected and tested at least once a year, as the manufacturer manuals cited on these pages set out.
Who does fire protection work in a UPS room?
Fire protection work is delivered through specialist fire protection subcontractors; the UPS and battery owner supplies the battery chemistry, the heat load and the power shutdown plan they need.
Sources, checked 2026-10-04:
- Manual Honeywell, Nexus FK-5-1-12 clean agent fire extinguishing system owner's manual HSN-MNL-F2-R4 (13 Feb 2024), p. 9-51
- Manual Honeywell, IG-541 inert gas fire extinguishing system manual HSN-MNL-IG541-R3 (15 Apr 2024), p. 9-44
- Reference Xtralis, VESDA-E VEP engineering specification 29172_04 (April 2016), p. 5-15
- Manual Firetrace, FK-5-1-12 indirect low pressure system design, installation, operation and maintenance manual 800027 (06/05/2023), p. 9-44
- White paper Vertiv, Lithium-ion batteries safety (white paper): fire code and battery management, p. 5-6
- Reference 3M, PFAS stewardship: Operations and innovation (page read 5 October 2026)
- Reference US EPA, SNAP program: Substitutes in Total Flooding Agents (page read 5 October 2026)
Need the UPS in this room serviced?
UPS service: reply and quote within 4 business hours; same day in Montreal, Quebec City, Toronto and Ottawa; 24 to 48 hours elsewhere. 1 (438) 800-0382