How long do UPS batteries last?

VRLA batteries in UPS use are replaced every four to five years on average, even though they are often sold with a 10-year design life. Heat, constant float charging, frequent discharges and poor power shorten that; a cool, steady room and good charging stretch it.

Key facts

Why do VRLA batteries fall short of their design life?

Because design life assumes laboratory conditions and UPS use is not that. Eaton's aging-UPS paper defines design life as the projected life under very limited use in pristine conditions, service life as the typical life under normal use, and a recommended replacement time with margin before failure; for VRLA those are 10, 5 and 4 years. Its battery paper confirms it in the field: in UPS applications, VRLA batteries are replaced every four to five years on average.

VRLA and lithium-ion life in UPS useEaton's average component life: VRLA batteries recommended replacement 4 years, service life 5, design life 10; lithium 10, 12 and 20 years.VRLA4510Lithium101220ReplaceService lifeDesign lifeYears, average, Eaton component-life table.
Average figures from Eaton's component-life table (years). Design life assumes laboratory conditions; plan with the recommended replacement time.

How much does temperature matter?

More than anything else you control. C&D recommends operating its VRLA batteries at 25 °C within plus or minus 5.5 °C as the best combination of performance and life; EnerSys gives 23-26 °C and states that elevated temperatures reduce operating life; Vertiv puts the VRLA ideal at 20-25 °C. A battery cabinet beside a hot UPS, or a room that drifts warm in summer, quietly takes years off every string.

How does charging wear a battery?

Constant float charging overcharges a battery that is already full. Eaton explains that a UPS battery may sit on float for months without a discharge, so trickle-charge energy is forced into a full battery, which slowly corrodes the positive grid and shortens float life. Some UPS use charging schemes that rest the battery between charges to reduce this; whatever the scheme, the float voltage must match the battery maker's figure for the temperature, as C&D's manual sets out.

What else shortens battery life?

Do flooded batteries last longer than VRLA?

Generally, yes, at a cost. Eaton notes that sealed (VRLA) batteries tend to be less expensive but wear out sooner, while flooded (vented lead-acid) batteries need specialised installation and maintenance; its component table gives wet cells an average recommended replacement of 12 years, against 4 for VRLA. Flooded strings are found mostly in large UPS plants with dedicated battery rooms; most data-centre UPS today use VRLA or lithium-ion.

What are the signs a string is due?

Readings, mostly. C&D's guidance on ohmic readings: a change of less than 20% over time is acceptable; more than 50% needs further attention, such as a load test. Other signs are blocks whose float voltage drifts from the rest, terminal temperatures above their neighbours, bulging or damaged jars, and a capacity test that falls short. Schneider Electric's advice for its UPS is simple: replace the battery immediately when the UPS says it is needed. How the readings are taken is in battery replacement and testing.

Is lithium-ion worth it for battery life?

Often. Vertiv puts lithium-ion UPS batteries at 8 to 10 years or more, 2-3x VRLA life, and Eaton's table gives an average recommended replacement of 10 years. The trade-offs are covered in lithium-ion vs VRLA. For VRLA replacement strings, see these replacement battery strings for data-centre UPS; for battery service across Canada, UPS battery repair and replacement.

Related pages

Questions

How many years do UPS batteries last?

VRLA batteries in UPS use are replaced every four to five years on average, by Eaton's data. Lithium-ion lasts about two to three times longer.

What temperature should a UPS battery room be?

About 25 °C, held steady: C&D gives 25 °C within plus or minus 5.5 °C, EnerSys 23-26 °C.

Does a UPS battery wear out if it is never used?

Yes. Constant float charging slowly corrodes the positive grid, so batteries age even without outages.

Can one battery block be replaced?

On a young string, sometimes. On an aged string, a new block among old ones tends to be mischarged, so the readings decide.