How long do UPS batteries last?

VRLA batteries in UPS use are replaced every four to five years on average, even though they are often sold with a 10-year design life. Heat, constant float charging, frequent discharges and poor power shorten that; a cool, steady room and good charging stretch it.

On this page
  1. Design life and service life
  2. Temperature
  3. Charging
  4. Other factors
  5. Flooded and VRLA batteries
  6. Signs a string is due
  7. Lithium-ion

Key facts

Real VRLA life:
Replaced every four to five years on average in UPS use, despite a 10-year design life (Eaton)
Life figures:
VRLA: recommended replacement 4, service life 5, design life 10 years (Eaton)
Best temperature:
25 °C, within plus or minus 5.5 °C (C&D)
Ambient range:
23-26 °C; elevated temperatures reduce operating life (EnerSys)
Cost weight:
The battery often accounts for 30% of the cost of the UPS (Eaton)

How Long Does a UPS Battery Last?

Design life and service life

Short answer

Design life assumes laboratory conditions that UPS use does not provide. Eaton's aging-UPS paper defines design life as the projected life under very limited use in pristine conditions, service life as the typical life under normal use, and a recommended replacement time with margin before failure; for VRLA those are 10, 5 and 4 years. Eaton's battery paper reports the field result: in UPS applications, VRLA batteries are replaced every four to five years on average.

Fig. 1 · VRLA and lithium-ion life in UPS use

VRLA and lithium-ion life in UPS useEaton's average component life: VRLA batteries recommended replacement 4 years, service life 5, design life 10; lithium 10, 12 and 20 years.VRLA4510Lithium101220ReplaceService lifeDesign lifeYears, average, Eaton component-life table.
Average figures from Eaton's component-life table (years). Design life assumes laboratory conditions; plan with the recommended replacement time.

Temperature

Of the factors a site controls, temperature matters most. C&D recommends operating its VRLA batteries at 25 °C within plus or minus 5.5 °C as the best combination of performance and life; EnerSys gives 23-26 °C and states that elevated temperatures reduce operating life; Vertiv puts the VRLA ideal at 20-25 °C. APC gives 20-25 °C as the optimal temperature for a lead-acid battery and, as a general rule, every 8 °C rise cuts its life in half; CSB warns that using a VRLA battery for a long period above 40 °C may cause thermal runaway. A battery cabinet beside a hot UPS, or a room that drifts warm in summer, shortens the life of every string in it.

Charging

Constant float charging overcharges a battery that is already full. Eaton explains that a UPS battery may sit on float for months without a discharge, so trickle-charge energy is forced into a full battery, which slowly corrodes the positive grid and shortens float life. Some UPS use charging schemes that rest the battery between charges to reduce this; whatever the scheme, the float voltage must match the battery maker's figure for the temperature, as C&D's manual sets out.

Other factors

  • Frequent short discharges and poor utility power, which Schneider Electric lists alongside heat.
  • Storage, acceptance testing, chemistry and cycling, which Eaton lists among the factors that set battery life.
  • Loose or corroded connections, which heat and stress the blocks around them.
  • Mixing new and old blocks in one string: the new block sits at a different voltage from its aged neighbours, so the charger cannot hold every block at its correct float voltage.
  • Long storage before installation, which Eaton lists among the life factors because the battery self-discharges while it waits.

Flooded and VRLA batteries

Flooded batteries generally last longer than VRLA, at a cost. Eaton notes that sealed (VRLA) batteries tend to be less expensive but wear out sooner, while flooded (vented lead-acid) batteries need specialised installation and maintenance; its component table gives wet cells an average recommended replacement of 12 years, against 4 for VRLA.

Signs a string is due

C&D's guidance on ohmic readings: a change of less than 20% over time is acceptable; more than 50% needs further attention, such as a load test. Other signs are blocks whose float voltage drifts from the rest, terminal temperatures above their neighbours, bulging or damaged jars, and a capacity test that falls short. Schneider Electric's advice for its UPS is to replace the battery immediately when the UPS says it is needed. See battery replacement and testing for how the readings are taken.

Lithium-ion

Vertiv puts lithium-ion UPS batteries at 8 to 10 years or more, 2-3x VRLA life, and Eaton's table gives an average recommended replacement of 10 years; see lithium-ion vs VRLA for the trade-offs. For VRLA replacement blocks, see these UPS replacement batteries by model; the signs that a string is near its end are checked during UPS battery testing and replacement.

Questions

How many years do UPS batteries last?

VRLA batteries in UPS use are replaced every four to five years on average, by Eaton's data. Lithium-ion lasts about two to three times longer.

What temperature should a UPS battery room be?

About 25 °C, held steady: C&D gives 25 °C within plus or minus 5.5 °C, EnerSys 23-26 °C.

Does a UPS battery wear out if it is never used?

Yes. Constant float charging slowly corrodes the positive grid, so batteries age even without outages.

Can one battery block be replaced?

On a young string, sometimes. On an aged string, a new block among old ones tends to be mischarged, so the readings decide.