Monitoring
Data centre monitoring
Monitoring tells you that something in the power path or the room has drifted before it becomes an outage. In a data centre or server room the UPS and its batteries come first, because they are what carries the load when the utility fails; the room around them comes next.
Need the UPS in this room serviced? Get a quote
Key facts
- Share of UPS failures that are battery related:
- Approximately 37 percent (Vertiv)
- Batteries maintained and remotely monitored:
- Zero outages due to bad batteries in Vertiv's study group
- What a UPS already watches:
- Power quality, load and battery health Schneider Electric
- Recommended IT inlet temperature (ASHRAE):
- 18 to 27 °C ASHRAE TC 9.9
- Where Level 1 PUE reads the IT load:
- At the UPS output The Green Grid
UPS service: reply and quote within 4 business hours; same day in Montreal, Quebec City, Toronto and Ottawa; 24 to 48 hours elsewhere.
The UPS and its batteries first
Vertiv states that approximately 37 percent of all UPS system failures are battery related, and that ongoing remote monitoring of UPS and battery health improves availability by detecting and correcting problems early. In its reliability study, sites whose batteries were professionally maintained and remotely monitored had zero outages due to bad batteries. A UPS already measures a great deal on its own: Schneider Electric's paper on physical threats notes that UPS systems monitor power quality, load and battery health. What is often missing is the path from the alarm to a person who knows what to do with it.
See remote UPS monitoring and alarm response, and the battery monitoring systems that read every block.
The room
In the room, the sensors cover temperature at the rack inlets, humidity, water leaks, doors and smoke, roughly in order of how often each causes trouble. Schneider Electric's guidance puts temperature sensors at the top, middle and bottom of each rack front, a humidity sensor in each cold aisle, leak rope around each cooling unit and under raised floors, and a switch on every entry door. See the server room monitoring guide for each sensor, where it goes and what threshold to start from, including the ASHRAE recommended range of 18 to 27 °C at the equipment inlet.
DCIM and BMS
A BMS runs the building and its mechanical plant; DCIM manages the data centre's physical assets, capacity and power down to the rack. Both can read the same UPS through its network card, using different protocols. See the DCIM vs BMS comparison for which system should own which alarm, and why a UPS alarm should reach someone directly even when both systems exist.
PUE
PUE is the efficiency figure that monitoring makes possible: total facility energy divided by the energy delivered to IT equipment. The Green Grid's most basic measurement level reads the IT load at the UPS output, so the UPS is again the starting point. See PUE explained, with a worked example for the formula, the three measurement levels and what a figure such as 1.26 says.
Quoting a monitoring set-up
A monitoring set-up is quoted with the UPS work it protects. Sensor installation and DCIM or BMS integration are delivered through specialist subcontractors, under one quote and one point of contact with the UPS and battery service. The quote lists the points monitored, the thresholds, who receives each alarm and what happens next. Send the UPS models, the number of battery strings and the room layout through the quote request.
In this section
PUE (power usage effectiveness) explained
The formula, the three levels and a worked example.
What to monitor in a server room
Temperature, humidity, leaks, doors, power: where each sensor goes.
DCIM vs BMS in a data centre
What each manages, the protocols, who owns the UPS alarm.
Remote UPS and battery monitoring
Network interfaces, alarm routing and response responsibilities.
Recorded: Models, card type, strings and blocks, network access
UPS battery monitoring systems
Per-block voltage, resistance and temperature, with alarms.
Questions
What should be monitored first in a data centre?
The UPS and its batteries. Vertiv puts approximately 37 percent of UPS system failures down to the battery, and the UPS is what carries the load when the utility fails. Room temperature, humidity, leaks and doors come next.
Does a UPS not monitor itself?
It measures power quality, load and battery health, but its alarms are only useful when they reach someone who can act. Remote monitoring closes that gap.
Is monitoring sold on its own?
It is quoted with the UPS and battery service it protects, so alarms lead straight to a response. Sensor installation and DCIM or BMS integration are delivered through specialist subcontractors.
Do I need DCIM to monitor a server room?
No. A small room can be covered by the UPS network card, a few sensors and alert routing. DCIM earns its cost when there are many racks, capacity questions and several systems to bring together.
Sources, checked 2026-10-04:
- Reference Vertiv, UPS Remote Monitoring service (vertiv.com, Canada)
- White paper Vertiv, The effect of regular, skilled preventive maintenance and remote monitoring on critical power system reliability (white paper), p. 2-6
- White paper Schneider Electric, White Paper 102 rev 3: Monitoring Physical Threats in the Data Center, p. 2-10
- White paper The Green Grid, White Paper #49: PUE, A Comprehensive Examination of the Metric (2012), p. 8-34
- White paper The Green Grid, White Paper #49, partial PUE usage example 1 (Figure 17), p. 65
- White paper ASHRAE TC 9.9, Data Center Power Equipment Thermal Guidelines and Best Practices (white paper, 2016), p. 10-38
Need the UPS in this room serviced?
UPS service: reply and quote within 4 business hours; same day in Montreal, Quebec City, Toronto and Ottawa; 24 to 48 hours elsewhere. 1 (438) 800-0382