Monitoring
Remote UPS and battery monitoring
Remote UPS monitoring forwards UPS and battery data and alarms through the installed equipment’s network interfaces. Confirm the connection, alarm thresholds, recipients and response responsibilities for the site before arranging monitoring work.
Need the UPS in this room serviced? Get a quote
Key facts
- Share of UPS failures that are battery related:
- Approximately 37 percent (Vertiv)
- Batteries maintained and remotely monitored:
- Zero outages due to bad batteries in Vertiv's study group
- Alert routes:
- Email, SMS, SNMP traps and HTTP posts Schneider Electric
- Network card heartbeat:
- A heartbeat trap, every 24 hours by default (Vertiv)
Remote UPS Monitoring
Remote monitoring and availability
Short answer
A UPS alarm helps only if someone acts on it in time. Vertiv states that approximately 37 percent of all UPS system failures are battery related, and that ongoing remote monitoring of UPS and battery health improves availability by finding and correcting problems early. Its reliability study found zero outages due to bad batteries on systems whose batteries were professionally maintained and remotely monitored, and noted the need for experts to read the alarm data correctly.
In a server room without staff, or a data centre whose operators watch a dozen other systems, an alarm on the UPS front panel can go unseen; remote monitoring sends it to someone whose job is the UPS.
Setting up remote monitoring
- StepSurvey the UPS, battery strings and networkWhat is agreed or recordedModels, card type, strings and blocks, network access
- StepSet the alarm list and severitiesWhat is agreed or recordedEach point, its thresholds and its level
- StepConfigure the network card and routesWhat is agreed or recordedRead-only access, changed SNMP strings, email, SMS and trap targets
- StepAgree the response planWhat is agreed or recordedWho is called for each level, escalation times, site access
- StepTest every alarm end to endWhat is agreed or recordedAlarm raised, received, acknowledged and logged
- StepGo live and reportWhat is agreed or recordedEvent log, monthly summary, findings for the next maintenance visit
Alarms watched
- UPS state: on battery, on bypass, overload, output out of tolerance, transfer events, fault codes.
- Battery: low battery, string and block voltage, block resistance and temperature where a battery monitoring system is fitted, discharge events.
- Environment: UPS room or battery cabinet temperature, and the room sensors described in the server room monitoring guide.
- The link itself: a heartbeat from the network card, so silence is noticed. Vertiv's Unity card sends a heartbeat trap every 24 hours by default.
Each alarm gets a severity. Schneider Electric's guidance is to allow several thresholds per point, informational, warning, critical and failure, so a battery temperature creeping up and a UPS on battery are not treated alike.
Routing and escalation
Alarms reach the people who respond by more than one route, with escalation. Alerts can travel as email, SMS text, SNMP traps or posts to an HTTP server, and each should say which unit, where and when. An alarm not acknowledged within a set time escalates to the next person on the list. Battery monitors can send their own alerts too; Vertiv's BDSU-50 guide describes an embedded email manager that delivers alerts and battery data on a defined priority to service technicians.
The network card is configured for this with security in mind: SNMP community strings changed from their defaults, read-only access for building systems, and the card on a network segment the site's IT team approves. If a BMS or DCIM also reads the UPS, see DCIM vs BMS for how the alarms are shared.
When an alarm comes in
An alarm response plan should define who checks each alarm, how it is classified and who is contacted. A battery block drifting out of range can lead to a planned visit and a battery test or replacement; a UPS on battery during a utility failure can require a call to the site contact and, if the event outlasts the runtime, an emergency UPS repair dispatch. Every event, the actions taken and the outcome should be logged, so the next maintenance visit starts with the history; see the preventive UPS maintenance guide for what that visit covers.
UPS monitoring configuration starts with the installed equipment, its available interfaces and the site’s alarm-routing needs. Confirm the connection scope and who receives and responds to alarms before arranging work; sensor or BMS requirements need separate scope confirmation.
Questions
Can any UPS be monitored remotely?
Most three-phase and many single-phase UPS can, through a network card or a serial interface. Older units may need a card or a gateway; the survey settles it.
Does remote monitoring replace maintenance?
No. It catches problems between visits and tells the next visit where to look. Vertiv's study found the best results with maintenance and remote monitoring together.
What if the network link fails?
The card's heartbeat stops arriving, which raises its own alarm.
Who installs the sensors and BMS links?
Sensor and BMS installation depends on the site’s equipment and the agreed scope. Confirm the installer and responsibilities before including it in a monitoring request.
What should be confirmed before monitoring work?
Confirm the installed UPS network card or interface, the alarm recipients, the escalation responsibilities and whether sensor or BMS links are within the agreed scope.
Sources, checked 2026-10-04:
- Reference Vertiv, UPS Remote Monitoring service (vertiv.com, Canada)
- White paper Vertiv, The effect of regular, skilled preventive maintenance and remote monitoring on critical power system reliability (white paper), p. 2-6
- Reference Vertiv, Liebert IntelliSlot Unity Card installer/user guide SL-52645, p. 5-18
- White paper Schneider Electric, White Paper 102 rev 3: Monitoring Physical Threats in the Data Center, p. 2-10
- Reference Vertiv, Albér Universal Battery Diagnostic System battery monitor (BDSU-50) installer/user guide, p. 11-19