Cooling
In-row and liquid cooling for high-density racks
Room cooling fills the room with cold air and relies on it reaching every inlet. That works at a few kilowatts per rack and fails at twenty or more. Higher densities move the cooling closer to the heat: into the row, into the rack, or onto the processor with liquid.
Need the UPS in this room serviced? Get a quote
On this page
Key facts
- Room cooling, uncontained:
- Effective at about 1-2 kW per rack (Schneider Electric)
- Row cooling for existing rooms:
- Worth considering from 5 kW per rack (Schneider Electric)
- Rack-based cooling:
- Up to 50 kW per rack (Schneider Electric)
- Room-based design range:
- On the order of 1-5 kW per rack (ENERGY STAR)
- Cold plates:
- Most run easily on W32 facility water (ASHRAE)
Room cooling limits
Short answer
Room cooling relies on mixing, and dense racks overwhelm it. Schneider Electric's White Paper 130 finds traditional room cooling effective at an average of 1-2 kW per rack, and states that with peak densities of 20 kW per rack or more, traditional cooling without containment, dependent on air mixing, no longer functions effectively. ENERGY STAR makes the same point for room systems designed for 1-5 kW per rack: they cannot keep up, and hot spots develop.
The first steps are containment and blanking (see hot and cold aisle containment); the next is a shorter air path.
- Air cooling
- Liquid cooling
In-row cooling
In-row cooling places units in the row, between the racks, each dedicated to the row it sits in. ENERGY STAR describes row-oriented cooling as each unit cooling one row, mounted among the racks, overhead or under the floor. Schneider Electric lists the benefits: shorter airflow paths that cut fan power, the full rated capacity usable, and capacity and redundancy, N+1 or 2N, targeted at the rows that need them.
That targeting is useful in mixed rooms. ENERGY STAR gives the example of putting mission-critical servers in a row with redundant cooling while less important loads sit in a row without it. For existing data centres, Schneider Electric suggests considering row-based cooling when deploying loads of 5 kW per rack and above.
Rack-based cooling
Rack-based cooling is built into, or attached to, the rack itself, so the airflow path is as short as it can be. Schneider Electric states that rack-based paths are shorter and exactly defined, immune to installation variation and room constraints, and achieve the highest density of the three architectures, up to 50 kW per rack. ASHRAE's liquid cooling paper mentions the closely coupled option for existing raised-floor rooms: supplementing or replacing raised-floor cooling with a coil such as a rear door heat exchanger.
Liquid cooling
Liquid cooling takes over when the heat has to be taken from the chip rather than from the air. ASHRAE TC 9.9's paper on the emergence of liquid cooling describes direct on-chip cold plates, which most of today's designs can run on W32 facility water, and immersion, in which the equipment sits in a fluid. It also states that there is a rack density, different for each solution, at which the first cost of liquid cooling falls below that of air-cooling the same load.
- Rear door heat exchanger: a coil on the back of the rack takes heat from the exhaust air; the room still sees air-cooled equipment.
- Direct-to-chip cold plates: liquid takes the processor heat directly. ASHRAE gives a hybrid example: CPUs on liquid, the rest of the system on air through a rear door heat exchanger. It also notes the downsides of cooling only the CPU by liquid: fan power stays high and less heat goes to the liquid.
- Immersion: broad temperature support, high heat capture and high density, in ASHRAE's words, with added complexity in deployment and service, fluid sealing in rack-based designs, and possible warranty questions over fluid compatibility.
High density and the UPS
High density puts more power in fewer racks, and more heat comes from the UPS that feeds them. Schneider Electric's cooling-load worksheet counts UPS and power distribution losses as part of the room's heat; at high density the UPS is usually larger and its losses larger with it. Liquid systems also bring pumps and coolant distribution units that need power, and a cooling path that must keep running through a utility failure, which belongs in the UPS and generator plan.
Distribution changes too: high-density racks draw more per circuit and usually per rack PDU; see rack PDU types, and the server room cooling sizing guide for the heat arithmetic.
The room as density rises
As density rises, predictability and redundancy become harder to assure. Schneider Electric notes that in uncontained rooms the assurance of cooling unit redundancy becomes a very complicated analysis that is difficult to validate, while row-based designs let N+1 or 2N redundancy be targeted at specific rows. Shorter air paths also mean the full rated capacity of each unit can be used, rather than part of it being lost to air that bypasses the equipment.
The power path changes in step. Dense racks are usually fed by higher-capacity circuits and rack PDUs, and the UPS that feeds them carries more load in fewer places, so a single cooling fault near those racks affects a larger share of the UPS load. The densest rows are therefore the ones to give redundant cooling, as ENERGY STAR's example of a mission-critical row suggests.
Choosing row, rack or liquid
The choice depends on the density now, the density expected, and the room. A room averaging a few kilowatts per rack with a few dense racks can often take in-row units next to those racks. A new high-density deployment may start with rack-based or rear-door cooling and leave space for liquid. Processor-level heat that air cannot carry calls for cold plates or immersion, with the facility water the paper describes.
Cooling design, installation and maintenance are delivered through specialist cooling subcontractors. On the power side, scalable modular UPS frames can grow with the rack density.
Questions
What counts as a high-density rack?
There is no single line. Schneider Electric finds room cooling effective at an average of 1-2 kW per rack and ineffective without containment at 20 kW per rack or more.
What is in-row cooling?
Cooling units placed within the row of racks, each dedicated to that row, so cold air travels a short distance to the equipment inlets.
How dense can rack-based cooling go?
Schneider Electric gives up to 50 kW per rack for rack-based cooling.
Is liquid cooling more expensive than air?
Not always. ASHRAE states that above a certain rack density, which varies by solution, liquid cooling has a lower first cost than air-cooling the same load.
Does liquid cooling need UPS power?
Its pumps and coolant distribution units need power, and cooling must continue through a utility failure, so they belong in the UPS and generator plan.
Sources, checked 2026-10-04:
- White paper Schneider Electric, White Paper 130: Choosing Between Room, Row, and Rack-based Cooling for Data Centers (rev 2), p. 2-5
- Reference US EPA ENERGY STAR, Install in-rack or in-row cooling (data centre energy measures)
- White paper ASHRAE TC 9.9, Emergence and Expansion of Liquid Cooling in Mainstream Data Centers (white paper, 2021), p. 13-25
- White paper Schneider Electric, White Paper 25: Calculating Total Cooling Requirements for Data Centers (rev 4), p. 2-6
Need the UPS in this room serviced?
UPS service: reply and quote within 4 business hours; same day in Montreal, Quebec City, Toronto and Ottawa; 24 to 48 hours elsewhere. 1 (438) 800-0382