Cooling
Data centre cooling and airflow
Every watt the IT equipment and the UPS draw ends up as heat that the cooling system has to remove, including the losses of the UPS itself.
Need the UPS in this room serviced? Get a quote
Key facts
- IT heat output:
- Equal to its power consumption in watts (Schneider Electric)
- UPS share of heat in a typical room:
- 13%, in Schneider Electric's 75 kW example
- Recommended IT inlet range (ASHRAE):
- 18 to 27 °C ASHRAE TC 9.9
- Lead-acid battery life:
- About half for every 8 to 10 °C above 25 °C (ASHRAE)
- Room cooling limit:
- Effective at about 1-2 kW per rack without containment (Schneider Electric)
Cooling and the UPS
The UPS adds heat to the room, its batteries age faster when warm, and a cooling failure raises its load. Schneider Electric's cooling-load paper counts UPS losses as part of the room's heat, 13% of the total in its typical example. ASHRAE's paper on power equipment says the life of UPS batteries is very sensitive to temperature, and gives the rule of thumb that lead-acid life halves for every 8 to 10 °C above 25 °C. The same paper notes that during an HVAC failure the IT equipment draws more power as its fans speed up, so the UPS carries more load just as the room heats.
The UPS room is therefore part of the cooled space.
Cooling capacity
A room needs cooling for the IT load, the UPS and power distribution losses, lighting and people, plus margins. See the server room cooling sizing guide for Schneider Electric's worksheet, including the UPS term, and its rule of thumb of 1.3 times the IT load for small rooms.
Cooling equipment
Most rooms use either a CRAC, with its own compressor, or a CRAH, fed with chilled water from a chiller plant. See the CRAC vs CRAH comparison for the differences, and the precision vs comfort cooling guide for why office air conditioning is a poor fit for IT and UPS rooms.
Airflow
Airflow decides whether cold air reaches the equipment inlets or mixes with hot exhaust on the way. Schneider Electric's paper on cooling architectures finds traditional uncontained room cooling effective at around 1-2 kW per rack, and says that at 20 kW per rack or more it no longer works without containment. See hot and cold aisle containment and in-row and liquid cooling for high-density racks.
Maintenance
A cooling system stays reliable with regular maintenance by people who know precision equipment. Vertiv points out that precision cooling has very different service needs from building air conditioning. The cooling maintenance guide lists what a visit covers for CRAC and CRAH units. Cooling design, installation and maintenance are delivered through specialist cooling subcontractors.
In this section
CRAC vs CRAH
Compressor in the unit, or chilled water from a plant.
Precision vs comfort cooling
Sensible capacity, control accuracy and duty cycle.
Server room cooling sizing
IT load, UPS losses, lighting, people and margins.
Hot and cold aisle containment
Hot aisle, cold aisle, blanking panels and floor leaks.
In-row and liquid cooling for high-density racks
Room, row and rack cooling, then rear-door, cold plate and immersion.
What a cooling maintenance visit covers
Filters, belts, sensors, refrigerant, coils, valves, drains.
Questions
Does the UPS need cooling?
Yes. Its losses are part of the room's heat load, UPS modules are cooled by forced air, and its batteries age faster when warm. ASHRAE puts the ideal for lead-acid batteries at 25 °C.
What temperature should a server room be?
ASHRAE recommends 18 to 27 °C at the IT equipment inlet. Battery rooms need the narrower range the battery maker specifies.
Can office air conditioning cool a server room?
Poorly. Vertiv notes that precision cooling puts about 95% of its capacity into the dry heat electronics produce; comfort systems spend much more on removing moisture.
Who does cooling work?
Cooling design, installation and maintenance are delivered through specialist cooling subcontractors.
Sources, checked 2026-10-04:
- White paper Schneider Electric, White Paper 25: Calculating Total Cooling Requirements for Data Centers (rev 4), p. 2-6
- White paper ASHRAE TC 9.9, Data Center Power Equipment Thermal Guidelines and Best Practices (white paper, 2016): cooling and the UPS, p. 10-24
- White paper ASHRAE TC 9.9, Data Center Power Equipment Thermal Guidelines and Best Practices (white paper, 2016), p. 10-38
- White paper Schneider Electric, White Paper 130: Choosing Between Room, Row, and Rack-based Cooling for Data Centers (rev 2), p. 2-5
- White paper Vertiv, Comfort vs. precision cooling: the service aspect (white paper), p. 2-6