Skip to content
1 (438) 800-0382FR FrançaisGet a quote

Power infrastructure

What is an arc flash study?

An arc flash study calculates how much energy an electrical fault could release at each point of a system where someone might work, then turns that into labels, boundaries and protective equipment ratings. In Canada it is done under CSA Z462, which is based on NFPA 70E, and NFPA 70B caps the time between studies at 5 years, sooner after any change to the system.

Need the UPS in this room serviced? Get a quote

On this page
  1. What the study produces
  2. Steps of the study
  3. Changes in CSA Z462:24
  4. Review interval
  5. UPS and battery rooms in the scope
  6. Maintenance and the study
  7. Who may do the work in Canada
  8. Quoting with UPS work

Key facts

CSA Z462:
The sixth edition, based on NFPA 70E and harmonized with the Canadian Electrical Code CSA Group
Minimum arc ratings:
4, 8, 25, 40 and 75 cal/cm2 replace the old PPE categories in Z462:24 CSA Group
Study interval:
Short-circuit studies and incident energy analyses at intervals not exceeding 5 years (NFPA 70B)
Battery rooms:
Z462:24 revised the energy thresholds for batteries and battery rooms CSA Group

What the study produces

Short answer

An arc flash study produces numbers and labels for every point where someone may work on energized equipment. The study models the system, calculates the fault current available at each panel, switchboard and disconnect, works out how long the protective device upstream takes to clear the fault, and from those calculates the incident energy a worker would face at a set distance. The results go on labels at each piece of equipment and into the site's electrical safety programme, where they set the approach boundaries and the arc rating of the clothing and face protection required. CSA Z462 is the standard that sets those safe work requirements in Canada.

Fig. 1 · Steps of an arc flash study

Steps of an arc flash studySix steps in sequence: collect data and the single-line diagram, short-circuit study, selectivity study, incident energy analysis, labels and PPE, then review; a dashed arrow returns to the start.Field data, single-lineShort-circuit studySelectivity studyIncident energyLabels and PPEReviewAgain within 5 years, or after a change
The study runs from field data to labels; NFPA 70B caps the interval for the short-circuit and incident energy studies at 5 years, sooner after a change.

Steps of the study

  • Field data: walk the site and collect the equipment ratings, cable lengths and sizes, transformer data and protective device settings, and bring the single-line diagram up to date.
  • Short-circuit study: calculate the fault current available at each bus.
  • Selectivity study: check the time-current settings of the breakers and fuses, so the device nearest the fault clears first and fast.
  • Incident energy analysis: calculate the energy at each point from the fault current and the clearing time.
  • Labels and PPE: print and fix the labels, and set the required arc rating for each task.
  • Review: redo the study within the required interval, and after any change.

Each step depends on the one before: a wrong cable length or an outdated breaker setting changes the fault current or the clearing time, and with it the labels.

Changes in CSA Z462:24

CSA Z462:24 changed the way protective equipment is specified, among other things. CSA lists the major revisions of the 2024 edition, the sixth: the arc flash PPE category numbers 1 to 5 were replaced with minimum arc ratings of 4, 8, 25, 40 and 75 cal/cm2, so a task now calls for a rating rather than a category. The edition also revised the energy thresholds for batteries, battery rooms and battery enclosures, added information on battery risk assessment, added hazard thresholds for several categories of power electronic equipment, and added guidance on assessing the condition of maintenance of electrical equipment. Each of those applies to a UPS room.

Review interval

The study is redone at intervals not exceeding 5 years, and whenever the system changes. Eaton's summary of NFPA 70B (2023) lists the short-circuit study and the incident energy analysis among the system studies whose intervals shall not exceed 5 years, and notes that a change on the utility side, such as a new transformer feeding the facility, also calls for updated studies. In a data centre the triggers are frequent: a new UPS, a larger generator, an added floor PDU, changed breaker settings or a utility upgrade all change the fault current or the clearing time somewhere downstream.

UPS and battery rooms in the scope

UPS and battery rooms hold both AC and DC hazards, and stored energy that does not switch off with the utility. A UPS can feed a fault from its battery after the input breaker opens, and a battery string is energized whenever it is connected. CSA Z462:24 revised its energy thresholds for batteries, battery rooms and battery enclosures and added battery risk assessment information, so the battery cabinets and DC breakers belong in the study alongside the AC switchgear. UPS and battery work therefore starts with the label on the equipment, which gives the technician the arc rating and the boundary before the cabinet is opened. See battery replacement and testing for the DC side of the UPS.

Maintenance and the study

A study assumes the breakers trip as designed, and a poorly maintained breaker may not. Eaton notes that NFPA 70E treats incident energy calculations as invalid if protective devices are not properly maintained, and that a breaker that is not properly lubricated or mechanically functioning can trip late, raising incident energy above what the analysis calculated. The study and the switchgear maintenance record are therefore read together. CSA Z462:24 also added guidance on assessing the condition of maintenance, which makes that link explicit.

Who may do the work in Canada

Arc flash work in Canada is done by qualified people under the provincial rules, with the study itself usually signed by an engineer. CSA Z462 sets criteria for identifying and training qualified electrical workers and for deciding which work only they may do, and tells users to refer to the provincial, territorial and federal safety regulations that apply to their site. Licensed electrical work and permits are provincial; in Ontario, the Electrical Safety Authority notes that almost all electrical work requires a notification of work. CSA also notes that Ontario data showed over 40% of electrical incidents between 2007 and 2011 happened during repair and maintenance, which is the work an arc flash study protects.

Quoting with UPS work

Arc flash studies are delivered through specialist engineering partners and quoted alongside the UPS and switchgear work, so the field data, the study and the labels follow the equipment changes. Send the single-line diagram, the site address and the date of the last study through the quote request form; for UPS work tied to the same equipment changes, see why planned UPS maintenance protects the electrical system.

Questions

Is an arc flash study mandatory in Canada?

CSA Z462 sets the requirements, and provincial occupational health and safety regulations govern how they apply; check the regulation for your province.

How often does an arc flash study need updating?

At intervals not exceeding 5 years under NFPA 70B, and sooner after any change to the electrical system.

What replaced the PPE categories in CSA Z462:24?

Minimum arc ratings of 4, 8, 25, 40 and 75 cal/cm2, replacing categories 1 to 5.

Does an arc flash study cover the UPS battery?

It should: Z462:24 revised the energy thresholds for batteries and battery rooms and added battery risk assessment information.

Sources, checked 2026-10-04:

Need the UPS in this room serviced?

UPS service: reply and quote within 4 business hours; same day in Montreal, Quebec City, Toronto and Ottawa; 24 to 48 hours elsewhere. 1 (438) 800-0382

Get a quote
Call 1 (438) 800-0382Get a quote