Skip to content
1 (438) 800-0382FR FrançaisGet a quote

Cooling

CRAC vs CRAH

A CRAC (computer room air conditioner) contains its own refrigeration compressor; a CRAH (computer room air handler) has no compressor and cools the air with chilled water supplied by a chiller. Both sit in or beside the IT space and push cold air to the equipment. The difference is where the refrigeration happens, and that changes cost, capacity, maintenance and how the system fails.

Need the UPS in this room serviced? Get a quote

On this page
  1. CRAC and CRAH
  2. CRAC and CRAH compared
  3. When a CRAC fits
  4. When a CRAH fits
  5. How each fails
  6. Maintenance differences
  7. Cooling a UPS and battery room

Key facts

CRAC:
Contains an on-board refrigerant compressor (LBNL)
CRAH:
Cools room air through chilled water coils (Schneider Electric)
Chilled water temperature:
About 8-15 °C from the chiller (Schneider Electric)
CRAH vs CRAC at the same footprint:
CRAH: lower cost, fewer parts, greater heat removal capacity Schneider Electric
Chilled water system cost:
Highest capital cost below 100 kW of IT load Schneider Electric

CRAC and CRAH

Short answer

The difference is where the refrigeration cycle sits. LBNL's master list of data centre energy measures states that, unlike CRAHs and air handlers, CRACs contain on-board refrigerant compressors. Schneider Electric's paper on cooling technologies describes the CRAH side: in a chilled water system the refrigeration components move from the computer room unit to a water chiller, which produces water at about 8-15 °C and pumps it to the CRAH units. The CRAH draws warm room air through its chilled water coils and sends the heat back to the chiller in the warmer return water.

A CRAC instead carries its own compressor and evaporator coil. In the most common arrangement, which Schneider Electric calls an air-cooled CRAC DX system, refrigerant runs from the indoor unit to a condenser outdoors or on the roof. DX stands for direct expansion.

Fig. 1 · CRAC and CRAH

Where the refrigeration happensA CRAC in the room holds a compressor and coil and sends refrigerant to an outdoor condenser. A CRAH in the room holds a chilled water coil fed by a chiller plant, which rejects heat through a cooling tower or dry cooler.CRAC (DX)CRAHCRACcompressor, coilRefrigerantCondenseroutdoorsCRAHchilled water coilChilledwaterChiller plantCooling toweror dry coolerOne unit, onerefrigeration circuitSeveral CRAHs can depend on one chiller plant.
  • In the IT or UPS room
  • Outside the room
A CRAC carries its own refrigeration; a CRAH depends on a chiller plant that may serve the whole building. Source: Schneider Electric White Paper 59; LBNL master list

CRAC and CRAH compared

CRAC (DX)CRAH (chilled water)
RefrigerationCompressor inside the unitChiller plant elsewhere in the building
Heat leaves the room byRefrigerant to a condenser, or glycol to a dry coolerChilled water back to the chiller
Decision checkTypical roomSmall and medium rooms; Schneider Electric calls the air-cooled CRAC the stapleLarge rooms and buildings with a chiller plant
CostLowest overall cost for the air-cooled typeHighest capital cost below 100 kW of IT load
Capacity per footprintLowerGreater heat removal capacity, fewer parts
Distance limitsRefrigerant piping cannot run long distances reliablyChilled water loops can run very long distances

The comparison follows Schneider Electric's White Paper 59: CRACs suit rooms that stand on their own, and CRAHs suit buildings that already run, or justify, a chiller plant.

When a CRAC fits

A CRAC fits a stand-alone server room or UPS room without a building chiller, and small and medium rooms generally. Schneider Electric lists the air-cooled DX system's advantages as the lowest overall cost and the easiest maintenance, and its limits as refrigerant piping that must be installed in the field and cannot run long distances reliably and economically. Where the condenser cannot be close, a glycol-cooled CRAC sends its heat to a glycol loop and an outdoor dry cooler instead.

For the smallest rooms there are also self-contained units with the whole refrigeration cycle in one box; Schneider Electric notes these are limited in capacity because of the space the refrigeration components and air ducts take.

When a CRAH fits

A CRAH fits where there is, or will be, a chiller plant, and where the IT load is large. Schneider Electric states that chilled water CRAH units generally cost less, contain fewer parts and have greater heat removal capacity than CRAC units of the same footprint, but that chilled water systems have the highest capital cost for installations below 100 kW of IT load. A CRAH also moves the compressors, and their maintenance, out of the IT space.

How each fails

A CRAC fails one unit at a time: a compressor, a fan, a refrigerant leak. Each unit is its own refrigeration system, so redundancy is a matter of having one more unit than the load needs. A CRAH depends on the chilled water plant: a chiller, a pump or the water supply can take several CRAHs down together, so the plant's own redundancy decides the room's.

In both cases the UPS room is affected. ASHRAE's paper on power equipment notes that during an HVAC failure the IT equipment draws more power as its fans speed up, which raises the load on the UPS just as the room starts to warm. The battery strings then sit in rising heat; see the UPS battery life guide for the effect on their life.

Maintenance differences

LBNL's table of cooling unit maintenance shares several items between the two, such as fan belts, air filters and sensor calibration, while refrigerant charge and the condenser coil apply to CRACs and the chilled water valve actuator to CRAHs. See the cooling maintenance guide for the full list. Cooling design, installation and maintenance are delivered through specialist cooling subcontractors. On the power side, data-centre UPS maintenance and repair covers the equipment the cooling protects.

Cooling a UPS and battery room

A UPS and battery room takes whichever type the building can support reliably, sized for the UPS losses as well as any IT load in the room. Schneider Electric's cooling-load worksheet gives the UPS heat as a fixed part tied to the UPS rating plus a part proportional to the load; the server room cooling sizing guide shows the arithmetic. A battery room also needs the narrow temperature range the battery maker specifies, which ASHRAE stresses because battery life is very sensitive to temperature.

Questions

What does CRAC stand for?

Computer room air conditioner: a cooling unit with its own refrigeration compressor.

What does CRAH stand for?

Computer room air handler: a unit that cools air with chilled water from a separate chiller, with no compressor of its own.

Which is cheaper, a CRAC or a CRAH?

For small rooms, an air-cooled CRAC: Schneider Electric gives it the lowest overall cost, while chilled water systems carry the highest capital cost below 100 kW of IT load.

Can a building chiller feed a CRAH in a server room?

Yes, if the chilled water is available around the clock. A chiller that shuts down at night or for maintenance leaves the room without cooling.

Is DX the same as CRAC?

Usually. DX means direct expansion; Schneider Electric notes that any system using refrigerant and an evaporator coil can be called DX.

Sources, checked 2026-10-04:

Need the UPS in this room serviced?

UPS service: reply and quote within 4 business hours; same day in Montreal, Quebec City, Toronto and Ottawa; 24 to 48 hours elsewhere. 1 (438) 800-0382

Get a quote
Call 1 (438) 800-0382Get a quote