Skip to content
1 (438) 800-0382FR FrançaisGet a quote

Power infrastructure

What is the difference between an ATS and an STS?

Both move a load from one power source to another. An automatic transfer switch (ATS) uses mechanical contacts and usually sits upstream of the UPS, choosing between the utility and the generator. A static transfer switch (STS) uses solid-state switches, transfers in a few milliseconds, and usually sits downstream of the UPS, choosing between two live UPS outputs.

Need the UPS in this room serviced? Get a quote

On this page
  1. Automatic transfer switch
  2. Open and closed transition
  3. Static transfer switch
  4. Position around the UPS
  5. STS and single-corded equipment
  6. ATS maintenance
  7. STS maintenance
  8. Quoting with the UPS

Key facts

Without a UPS:
Loads lose power for approximately 10 seconds while the generator starts and the ATS transfers Cummins
STS transfer time:
Less than 4 milliseconds, approximately one-quarter cycle (LayerZero)
Closed transition:
Momentary paralleling of both sources, under 100 ms, sources synchronized first Cummins
ATS maintenance:
Annual inspection and maintenance with measured electrical values (ASCO)
Monthly operation:
Transfer switches shall be operated monthly (standby power standard, via Cummins)

ATS and STS

Automatic transfer switch

Short answer

An automatic transfer switch moves the building load from the utility to the generator when the utility fails, and back when it returns. The ATS senses the outage, signals the generator to start, waits for the generator to reach the proper voltage and frequency, then transfers. Cummins notes that without a UPS, power to the loads is lost for approximately 10 seconds while that happens. In a data centre the UPS carries the IT load through the gap, which is why the ATS sits upstream of the UPS and the UPS battery only needs to last until the generator is on line. See UPS and generator compatibility for how the UPS should behave on generator power.

Fig. 1 · Where the ATS and the STS sit

Where the ATS and the STS sitUtility and generator feed an automatic transfer switch ahead of UPS A; UPS A and UPS B feed a static transfer switch, which feeds a PDU and a single-corded load.UtilityGeneratorATS (mechanical)UPS AUPS BSTS (solid state)PDUSingle-corded loadATS: utility to generator, mechanical contactsSTS: two live sources, transfer under 4 ms
The ATS chooses between utility and generator ahead of the UPS; the STS chooses between two live UPS outputs after it, fast enough for single-corded IT loads.

Open and closed transition

Open and closed transition are the two ways of making the transfer, with and without a break. Cummins lists three open-transition types: open-delayed, open-fast-transition with sync and open-fast-transition without sync. All of them break before they make, so the load sees a short interruption, and the delayed version pauses in a centre position to let motor loads spin down. Closed transition makes before it breaks: both sources are synchronized in phase, voltage and frequency, then paralleled momentarily, under 100 ms, so downstream loads see no gap. Cummins notes that some utilities require closed transition for their interconnect rules and that local service requirements must be checked first, because paralleling with the utility is regulated.

Static transfer switch

A static transfer switch moves the load between two live sources faster than IT equipment can notice. LayerZero describes the static transfer switch as a solid-state system that transfers critical loads between independent live sources in less than 4 milliseconds, approximately one-quarter cycle, using silicon-controlled rectifiers. LayerZero notes that servers and sensitive controls often tolerate only a few milliseconds of disturbance before they trip or reboot, hence the speed. An ATS is generally intended for utility-to-generator transfer; an STS is used between two sources that are both already running, such as two UPS systems.

Position around the UPS

Automatic transfer switch (ATS)Static transfer switch (STS)
Switching deviceMechanical contactsSolid-state (SCR)
Typical positionUpstream of the UPSDownstream of two UPS systems
SourcesUtility and generatorTwo live sources, usually two UPS outputs
TransferOpen (with a break) or closed (paralleled briefly)Less than 4 milliseconds
ProtectsThe building from a long outageSingle-corded IT loads from a source failure

The UPS sits between them. On a utility failure, the UPS battery carries the load while the ATS brings the generator on; on a UPS failure, the STS moves single-corded loads to the second UPS.

STS and single-corded equipment

Some equipment has only one cord and needs a transfer solution. The Uptime Institute notes that single-corded devices are found in a larger share of installations than should be expected, and that some owners use large static transfer switches, or STS power distribution units, to give them dual power paths. It also points out the trade-off: a large STS concentrates risk, while a rack-mounted or point-of-use transfer switch spreads it as low as possible in the distribution. Vertiv adds an engineering detail: switching between sources can saturate the downstream transformer and cause an inrush current that overloads the sources and trips upstream breakers, which is why STS transfer timing is designed around the transformer.

ATS maintenance

An ATS gets an annual inspection that includes measurements. ASCO's maintenance paper cites NFPA 110 for annual ATS inspection and maintenance including the measurement of specific electrical values, and recommends more frequent visits where the environment is severe. NFPA 110, as reprinted by Cummins, also requires transfer switches to be operated monthly. A thorough visit inspects the main and arcing contacts for wear, pitting and discoloration, checks the transfer mechanism, and measures the contact resistance across the main and arcing contacts. Where the switch has a bypass-isolation design, Cummins notes that the ATS can be drawn out for service while the load is fed through the bypass switch, so maintenance does not need an outage.

  • Visual inspection of insulation, arc chutes and the transfer mechanism, with the switch in bypass where the design allows it
  • Contact inspection and contact resistance measurement
  • Monthly operation and a timed transfer test with the generator
  • Controller event logs reviewed: Eaton notes that modern transfer switch controllers record time-stamped events and waveforms

STS maintenance

An STS is maintained as power electronics, much like a UPS. The switching devices have no contacts to wear, but the fans, the control boards and the connections age, and the transfer has to be proven. A visit typically reviews the event log, checks the fans and filters, scans the connections, and runs a controlled transfer between sources with both available. Because the STS sits right before the PDUs, it is usually serviced in the same window as the UPS that feeds it; UPS transfer switches and maintenance bypass panels are listed separately.

Quoting with the UPS

Transfer switch maintenance is delivered through specialist partners and quoted with the UPS work, so the transfer test, the generator run and the UPS check can be planned as one sequence. Send the switch make, model and rating through the quote request form.

Questions

How fast is a static transfer switch?

LayerZero puts it at less than 4 milliseconds, approximately one-quarter cycle, using solid-state switching.

Does an ATS interrupt the load?

An open-transition ATS breaks before it makes, so there is a short interruption; a closed-transition ATS parallels both sources for under 100 ms and does not.

Why is the UPS needed if there is an ATS?

Because the generator must start before the ATS can transfer; Cummins puts the gap at approximately 10 seconds without a UPS.

How often should an automatic transfer switch be maintained?

Annually, with measured electrical values, per NFPA 110 as cited by ASCO, and operated monthly; severe environments call for more frequent visits.

Sources, checked 2026-10-04:

Need the UPS in this room serviced?

UPS service: reply and quote within 4 business hours; same day in Montreal, Quebec City, Toronto and Ottawa; 24 to 48 hours elsewhere. 1 (438) 800-0382

Get a quote
Call 1 (438) 800-0382Get a quote