UPS runtime calculator
Estimate how long a UPS battery can carry a load from the battery's stored energy, the inverter efficiency and the load. It gives a first estimate for planning; the maker's runtime table for your UPS and battery is the figure to rely on.
Estimate the runtime
How the estimate is calculated
The calculator works out the usable energy in the battery and divides it by the power the inverter draws to carry the load. Stored energy is the number of strings times the blocks per string times each block's nominal voltage and amp-hour capacity; the usable share and the inverter efficiency reduce it; the result, divided by the load, gives minutes. Enter the amp-hour rating from the battery datasheet and the inverter efficiency from the UPS datasheet.
Limits of the estimate
Real capacity depends on the discharge rate, the temperature and the battery's age. A battery delivers less of its rated amp-hours at the high rates a UPS draws, and less when cold or worn, which is why makers publish runtime tables for each UPS and battery combination. The way to know what an installed string delivers is a capacity test, for which battery makers give a procedure or point to the IEEE one; see battery testing.
Typical runtime
Eaton puts a typical UPS battery at five to 15 minutes of backup, with external battery modules or cabinets adding up to several hours at full load. Data-centre UPS are usually sized to carry the load through the generator start with margin; server rooms without a generator need enough for a clean shutdown.
Battery temperature and runtime
Temperature changes both the capacity available today and the battery's life. C&D recommends operating at 25 °C within plus or minus 5.5 °C as the best balance of performance and life; colder batteries deliver less, hotter ones age faster. See UPS battery life for the details.
Questions
How accurate is the runtime calculator?
It is an energy estimate. Real runtime is lower at high discharge rates, at low temperature and as the battery ages; use the maker's runtime table to plan and a capacity test to prove it.
Where do I find the amp-hour rating?
On the battery block's label or datasheet. Use the rating at the discharge rate closest to your UPS's, where the datasheet gives several.
Why does my UPS show a different runtime?
The UPS estimates runtime from its own model of the battery and the measured load; after a capacity test or a battery replacement its estimate may need recalibration.
Sources, checked 2026-10-04:
- White paper Eaton, UPS basics (white paper WP153005EN), p. 2-5
- Manual EnerSys, VRLA battery systems safety, storage, operating and maintenance manual US-VR-OM-002 (March 2008), p. 6-35
- Manual C&D Technologies, msEndur II VRLA batteries installation and operating manual RS02044/0418, p. 6-25