UPS runtime calculator

Estimate how long a UPS battery can carry a load from the battery's stored energy, the inverter efficiency and the load. It gives a first estimate for planning; the maker's runtime table for your UPS and battery is the figure to rely on.

Estimate the runtime

Example values, worked by hand. Replace them with your own.

On the UPS output
Battery strings
Batteries in each string
Nominal, per block
At the rate on the datasheet
From the UPS datasheet
Share of the capacity you plan to use
Optional: start and transfer time

Estimated runtime: …

How this is calculated

Runtime in minutes = strings × blocks per string × block voltage × capacity in Ah × usable share × inverter efficiency ÷ load in watts × 60.

An energy estimate only. Battery capacity falls at high discharge rates, at low temperature and with age, so the maker's runtime table for your exact UPS and battery is the number to plan with.

Get a battery test quote

How the estimate is calculated

The calculator works out the usable energy in the battery and divides it by the power the inverter draws to carry the load. Stored energy is the number of strings times the blocks per string times each block's nominal voltage and amp-hour capacity; the usable share and the inverter efficiency reduce it; the result, divided by the load, gives minutes. Enter the amp-hour rating from the battery datasheet and the inverter efficiency from the UPS datasheet.

Fig. 1 · UPS battery strings

UPS battery stringsTwo battery strings, each of blocks in series, connect in parallel to the DC bus, which feeds the UPS inverter.String ABlockBlockBlockString BBlockBlockBlockDC busInverterEnergy = strings x blocks x block volts x amp-hours.
Blocks in series set a string's voltage; strings in parallel add capacity and runtime. The calculator multiplies them the same way.

Limits of the estimate

Real capacity depends on the discharge rate, the temperature and the battery's age. A battery delivers less of its rated amp-hours at the high rates a UPS draws, and less when cold or worn, which is why makers publish runtime tables for each UPS and battery combination. The way to know what an installed string delivers is a capacity test, for which battery makers give a procedure or point to the IEEE one; see battery testing.

Typical runtime

Eaton puts a typical UPS battery at five to 15 minutes of backup, with external battery modules or cabinets adding up to several hours at full load. Data-centre UPS are usually sized to carry the load through the generator start with margin; server rooms without a generator need enough for a clean shutdown.

Battery temperature and runtime

Temperature changes both the capacity available today and the battery's life. C&D recommends operating at 25 °C within plus or minus 5.5 °C as the best balance of performance and life; colder batteries deliver less, hotter ones age faster. See UPS battery life for the details.

Questions

How accurate is the runtime calculator?

It is an energy estimate. Real runtime is lower at high discharge rates, at low temperature and as the battery ages; use the maker's runtime table to plan and a capacity test to prove it.

Where do I find the amp-hour rating?

On the battery block's label or datasheet. Use the rating at the discharge rate closest to your UPS's, where the datasheet gives several.

Why does my UPS show a different runtime?

The UPS estimates runtime from its own model of the battery and the measured load; after a capacity test or a battery replacement its estimate may need recalibration.

Sources, checked 2026-10-04: