Skip to content
1 (438) 800-0382FR FrançaisGet a quote

Guides

How is power delivered in a data centre?

Power reaches a data-centre IT load through a chain: utility and generator, transfer switching, the UPS, then distribution down to the rack. The architecture decides how many of those links can fail or be maintained without the load noticing.

On this page
  1. Links in the power chain
  2. UPS arrangements
  3. Centralised and distributed UPS
  4. Dual paths and dual-corded equipment
  5. What the generator sees from the UPS
  6. Where the risk usually sits

Key facts

Generator gap:
The UPS carries the load until the generator is online Eaton
UPS architectures:
Zone, serial and parallel (Eaton)
Tier III and IV paths:
Dual power paths to the IT equipment Uptime Institute
Single-corded gear:
Point-of-use transfer switches keep the risk as low as possible in the distribution (Uptime)
Load types the generator sees:
UPS rectifiers (harmonics), capacitive filters and IT power supplies (leading power factor)

Data Centre Power Architecture

Fig. 1 · Dual-path power architecture

Dual-path power architecturePath A and path B each run from a source through a UPS and a PDU; a dual-corded server takes one cord from each; a single-corded device is fed through a point-of-use transfer switch connected to both paths.Path ASourceUPSPDUPath BSourceUPSPDUDual-corded serverPoint-of-use transfer switchSingle-corded
Two independent paths reach the dual-corded load. Single-corded equipment needs a point-of-use transfer switch to benefit from both. Source

UPS arrangements

Eaton's UPS basics paper describes three redundant arrangements:

ArchitectureHow it worksWhat a failure does
ZoneOne or more UPS dedicated to a set of resourcesThe impact is limited to that zone
SerialUPS connected end to endIf one fails, the others compensate automatically
ParallelIndependent UPS feeding a common output bus, synchronised to share the loadAny one UPS can fail or be isolated while the others carry the load

Eaton also notes that a centralised design uses larger UPS than a distributed one. Dual delivery paths, as in Tier III and IV sites, add a second complete path; each path can carry the load.

Centralised and distributed UPS

Centralised and distributed designs place risk differently. A centralised design puts large UPS in one plant room and distributes protected power across the building; Eaton notes that it uses larger kVA UPS than a distributed scheme, where smaller UPS sit closer to the loads they protect. Centralised plant is easier to maintain and monitor in one place; distributed systems limit how much load one failure can reach, much as the zone arrangement does.

Dual paths and dual-corded equipment

A second power path does nothing for a device with one power cord. Uptime Institute notes that Tier III sites use dual power paths for concurrent maintainability, that Tier IV adds autonomous response to failures, and that single-corded devices turn up in more installations than they should. Large static transfer switches upstream are one way owners try to give single-corded loads two sources; Uptime describes rack-mounted or point-of-use transfer switches as the way to keep that risk as low as possible.

What the generator sees from the UPS

Cummins lists the data-centre loads a generator must carry: UPS rectifiers that create harmonics, capacitive filters and IT power supplies with a leading power factor, and constant-power loads. It warns that low kW with high leading kVAR is a risk for the alternator, and suggests a generator mode on the UPS where available. Eaton's generator guidance adds that the generator must hold voltage and frequency inside the UPS's input window, or the UPS stays on battery; see UPS and generator compatibility.

Where the risk usually sits

  • In single points: one switchboard, one bypass, one breaker that every path passes through.
  • In single-corded equipment on a dual-path site.
  • In maintenance: the hours a path or UPS is on bypass, when one fault drops the load.
  • In untested assumptions: a generator never run under UPS load, a battery never proven by a capacity test.

Uptime Institute notes that the long-term value of a site depends on how it is operated. Sizing that UPS layer in kW and kVA, through to installation, is covered in three-phase UPS sizing and installation projects.

Questions

What is a 2N power architecture?

Two complete power paths, each able to carry the full load, so either can fail or be maintained. Redundancy counting is explained in the N+1 and 2N guide.

Do dual power paths need dual-corded servers?

Yes, to protect the server itself. A single-corded device on a dual-path site depends on one path, unless a point-of-use transfer switch feeds it.

Where does the UPS sit in the chain?

Between the utility-generator transfer and the distribution to the racks, carrying the load through the generator start and conditioning the supply.

Why does generator compatibility matter?

Because a generator that cannot hold the UPS's input window leaves the UPS on battery, and some UPS input characteristics are hard on alternators.

Sources, checked 2026-10-04:

Need a UPS serviced, tested or replaced?

Tell us the site, the UPS and the timing. We reply and quote within 4 business hours, or call 1 (438) 800-0382

Timing

We reply and quote within 4 business hours.

More details
Call 1 (438) 800-0382Get a quote