Skip to content
1 (438) 800-0382FR FrançaisGet a quote

Audits and planning

How do you check a data centre against its Tier claim?

A Tier audit tests the built site against what each Tier requires, path by path, rather than counting equipment. Uptime Institute defines four levels, from Tier I (Basic Capacity) to Tier IV (Fault Tolerant), and is explicit that adding components does not by itself reach any Tier, because distribution paths and other elements are evaluated too. An audit finds where a site claimed as Tier III or IV would not meet the definition, without certifying it.

Need the UPS in this room serviced? Get a quote

On this page
  1. Claims and certification
  2. What each Tier requires of the power path
  3. Component count and the Tier
  4. What the audit looks for on site
  5. Single-corded and miscorded loads
  6. The emergency power off
  7. Downtime per year
  8. Requesting a Tier audit

Key facts

Tier levels:
Tier I Basic Capacity, II Redundant Capacity, III Concurrently Maintainable, IV Fault Tolerant Uptime Institute
Component count:
Increasing the component count does not determine or guarantee any Tier level Uptime Institute
Tier II limit:
Concurrent maintenance of capacity components, not of distribution pathways Uptime Institute
Single-corded loads:
Rack-mounted transfer switches are the concession for odd numbers of cords (1,3,5)
Miscorded servers:
1-10% of servers may have both cords on the A distribution Uptime Institute

Claims and certification

Short answer

Uptime Institute notes that it is easy to claim Tier compliance, and a different matter to lay a solution open to a rigorous review. It is also the only organization permitted to certify data centres against its Tier Classification System, so anything else, including this kind of audit, is a check against the published definitions rather than a certification. The check serves owners buying colocation, tenants planning maintenance windows, and operators whose design has changed since it was built. For the definitions themselves, see data-centre Tiers.

Fig. 1 · What each Tier adds

What each Tier addsFour stacked levels: Tier I with a UPS, an engine generator and dedicated cooling; Tier II with redundant components; Tier III with a redundant delivery path for concurrent maintenance; Tier IV with fault tolerance.Tier IV: fault tolerantTier III: second delivery pathTier II: redundant componentsTier I: UPS, generator, coolingDefinitions: Uptime Institute Tier Classification System
Each Tier builds on the one below. An audit checks the built site against the level claimed, path by path, not by counting components.

What each Tier requires of the power path

In Uptime Institute's summary, Tier I includes a dedicated IT space, a UPS to filter spikes, sags and momentary outages, dedicated cooling, and an engine generator. Tier II adds redundant critical power and cooling components. Tier III adds a redundant delivery path, so that no shutdowns are needed for equipment replacement and maintenance. Tier IV adds fault tolerance, so that equipment failures and path interruptions stop short of the IT operations.

TierWhat it addsWhat the audit tests
Tier IUPS, engine generator, dedicated coolingThat each exists and serves the critical load
Tier IIRedundant power and cooling componentsThat each component can be taken out with spare capacity left
Tier IIIA redundant delivery pathThat every component and path can be shut down for work without affecting IT
Tier IVFault toleranceThat a single failure anywhere stops short of the IT load

Component count and the Tier

Uptime Institute calls Tier Certification a performance-based evaluation, not a checklist, and states that increasing the component count does not determine or guarantee any Tier level, because distribution pathways and other elements are evaluated too. Its own example is Tier II: it allows concurrent maintenance of capacity components such as engine generators, UPS, chillers and pumps, but not of switchboards, panels, transfer switches, transformers, bus bars, cables and pipes. A site with redundant UPS modules but one switchboard downstream may still need a computer-room shutdown to service that switchboard.

What the audit looks for on site

  • Distribution paths: trace each path from the utility and generator to the rack, and mark every switchboard, panel, transfer switch and cable that has no alternate.
  • Concurrent maintenance: for each component and path, ask whether it can be shut down for work while the IT load stays up, and how.
  • Single-corded loads: count the devices with one cord or an odd number of cords and check how they reach two paths.
  • Cording errors: sample dual-corded servers for both cords on the same side.
  • EPO: check that the emergency power off can be maintained or isolated without dropping the load.
  • Operations: procedures, maintenance records and staffing.

A UPS pair is redundant only as far as the paths below it are, so the audit continues past the UPS output to everything Tier III and Tier IV require downstream.

Single-corded and miscorded loads

Uptime Institute's Tier Standard includes a concession for equipment with odd numbers of cords (1,3,5) in the form of rack-mounted transfer switches, but Tier III and Tier IV sites must still have multiple, independent feeds to the rack. Miscording is harder to see. Uptime Institute cites anecdotal evidence that 1-10% of servers in a data centre may be improperly corded, with both cords plugged into the A distribution, so the server goes down with side A despite having two power supplies. A sample check during the audit finds them; rack PDUs with outlet-level monitoring make them easier to spot afterwards.

The emergency power off

The emergency power off is a single point that can drop the whole load. Uptime Institute reports that accidental EPO activation is a recurring cause of downtime, and its Tier Standard requires that the EPO system can be maintained, isolated or removed without affecting the critical load in Tier III, with Tier IV also requiring a fault-tolerant EPO system. An audit checks how the EPO is wired, what it shuts down, how it is protected against accidental activation and how it is tested.

Downtime per year

Neither a Tier audit nor the Tiers predict downtime per year. Uptime Institute removed references to expected downtime per year from the Tier Standard in 2009 and notes they were never part of the definitions. What an audit can say is which single failures or maintenance tasks would affect the IT load today, and what it would take to remove each one.

Requesting a Tier audit

Send the claimed Tier or redundancy level, the single-line diagram and the UPS and generator list through the audit quote request. The power path is covered directly; cooling and fire-protection findings go into the same report and are routed to the matching specialist service. For the UPS side of a data centre, see UPS maintenance and repair for data centres.

Questions

Can an audit certify my data centre as Tier III?

No. Uptime Institute is the only organization permitted to certify against its Tier Classification System; an audit checks the site against the published definitions and lists the gaps.

Does having redundant UPS modules make a site Tier III?

No. Uptime Institute states that component count does not determine any Tier; Tier III also needs a redundant delivery path so every component and path can be maintained without affecting IT.

What is the difference between Tier II and Tier III?

Tier II allows concurrent maintenance of capacity components only; Tier III adds a redundant delivery path, so switchboards, panels and cables can also be maintained without a shutdown.

How common is miscording?

Uptime Institute cites anecdotal evidence that 1-10% of servers may have both cords on the A distribution.

Sources, checked 2026-10-04:

Need the UPS in this room serviced?

UPS service: reply and quote within 4 business hours; same day in Montreal, Quebec City, Toronto and Ottawa; 24 to 48 hours elsewhere. 1 (438) 800-0382

Get a quote
Call 1 (438) 800-0382Get a quote